Permit: T06CM06031

Parcel: 128102960

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/17/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/04/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO MESSAGE LEFT
THERE IS NO INTERMEDIATE FOR ME TO LOOK AT
12/20/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS & FLOORS EXCEPT
AS NOTED FOR VDV CABELING
12/19/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
BLDG LOCKED
12/19/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROTECT M/C CABLE AT BASE PLATES
2. VERIFY IF BOXES ARE RATED FOR NO BOND
BUSHING OVER 250V -- 250.97

* PLEASE OPEN FLOOR FOR INSPECTIONS
* OLD VDV CABELING TO BE AS PER 725.3 & 6, 800.3&6
FLOOR AND CEILING
* LIGHT FIXTURES: NO CORDS ALLOWED ABOVE CEILING INSTALL AS PER MANUFACTURE.