Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM06013
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/30/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
05/18/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO INSTALL CEILING TILES CORRECTIONS #8 & #10 FROM PREVIOUS INSPECTION STILL TO BE CHECKED. |
|
05/14/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION -- DO NOT INSTALL TILES 1. SECURE (STRAP) M.C WITHIN 12" OF TERMINATIONS, STRAPS TO BE EFFECTIVE, NOT LOOSE -- NEC 330.30 2. INSTALL ALL J-BOX COVERS FOR INSPECTION 3. ADD EXTENSION RING ON OVERFILLED BOXES 4. FINISH DEMO ABOVE CEILING 5. CHECK ROOM 3816 HAVE ROMEX ABOVE CEILING 6. LOW VOLTAGE WIRING -- FINISH ALL ABOVE CEILING, DEMO ALL ABANDONED, LOW VOLTAGE TO BE SUPPORTED OFF GRID 7. SEAL ALL UNUSED OPENINGS AND RACEWAYS STUBS 8. SUB-PANEL FED DIFFERENTFROM WHAT PLAN SHOWS - PROVIDE REVISION AND HAVE PANE 32 & 32B OPEN FOR INSPECTION. 9. EMT TO BE STRAPPED WITHIN 36" OF ENCLOSURES 10. #6 & SMALLER GROUND TO BE GREEN OR BARE ENTIRE LENGTH. |