Permit: T06CM06013

Parcel: 11615088L

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
05/30/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
05/18/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO INSTALL CEILING TILES
CORRECTIONS #8 & #10 FROM PREVIOUS INSPECTION STILL TO BE CHECKED.
05/14/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION -- DO NOT INSTALL TILES
1. SECURE (STRAP) M.C WITHIN 12" OF TERMINATIONS, STRAPS TO BE EFFECTIVE, NOT LOOSE -- NEC 330.30
2. INSTALL ALL J-BOX COVERS FOR INSPECTION
3. ADD EXTENSION RING ON OVERFILLED BOXES
4. FINISH DEMO ABOVE CEILING
5. CHECK ROOM 3816 HAVE ROMEX ABOVE CEILING
6. LOW VOLTAGE WIRING -- FINISH ALL ABOVE CEILING, DEMO ALL ABANDONED, LOW VOLTAGE TO BE SUPPORTED OFF GRID
7. SEAL ALL UNUSED OPENINGS AND RACEWAYS STUBS
8. SUB-PANEL FED DIFFERENTFROM WHAT PLAN SHOWS - PROVIDE REVISION AND HAVE PANE 32 & 32B OPEN FOR INSPECTION.
9. EMT TO BE STRAPPED WITHIN 36" OF ENCLOSURES
10. #6 & SMALLER GROUND TO BE GREEN OR BARE ENTIRE LENGTH.