Permit: T06CM06012

Parcel: 106101280


Addresses:

1997 W PRICE ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/07/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
1. PROVIDE ONLY 45 AMP. FUSES FOR FAN COIL DISCONNECT.
2. PROVIDE A BUSHING IN CABINET OF FAN COIL WHERE DISCHARGE LINE CONNECTS.
3. SECURE SEAL TITE 12" FROM EACH END.
4. ELEC. INSPECTOR WILL CHECK CORRECTIONS.

OK FOR FINAL