Permit: T06CM06012

Parcel: 106101280


Addresses:

1997 W PRICE ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/08/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/07/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SECURE FIXTURES TO GRID -- NEC 110, 300
2. SECURE SUPPORT WIRES BOTH ENDS - NEC 300
3. PROPERLY GROUND BOXES - NEC 250, 110
4. NEUTRALS NOT TO BE SHARED UNDER SAME SCREW IN PANEL -- NEC 408
5. NEED GE BREAKERS IN GE PANEL -- NEC 110
6. AC NOT TO BE IN FRONT OF DISCONNECT -- NEC 110
7. SELF TAP SELF TAP SCREWS NOT ALLOWED ON GROUND NEC 250.8
8. SECURE MC WITHIN 12" OF TERMINATIONS - NEC 330
9. NEED SERVICE RECEPTACLE FOR AIR HANDLER - NEC 210.63
10. AIR HANDLER DISCONNECT TO HAVE PROPER WORKING CLEARANCE - NEC 110
DON'T DOUBLE GROUNDING CONDUCTORS -- NEC 110
03/05/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REMOVE CEILING TILES
2. HAVE PANELS OPEN FOR INSPECTION
3. STILL NEED REVISED PLANS
4. PLUG CHECK RECEPTACLES - HAVE REVERSE POLARITY ALSO, HAVE LOOSE RECEPTACLES, CRACKED COVERS
5. FINISH ALARM WIRING
6. INSTA-HOT CKT/WIRING UNDERSIZED
7. HAVE DEAD RECEPTACLES
8. C.B BELOW PANEL TO BE ACCESSIBLE.