Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/08/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/07/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SECURE FIXTURES TO GRID -- NEC 110, 300 2. SECURE SUPPORT WIRES BOTH ENDS - NEC 300 3. PROPERLY GROUND BOXES - NEC 250, 110 4. NEUTRALS NOT TO BE SHARED UNDER SAME SCREW IN PANEL -- NEC 408 5. NEED GE BREAKERS IN GE PANEL -- NEC 110 6. AC NOT TO BE IN FRONT OF DISCONNECT -- NEC 110 7. SELF TAP SELF TAP SCREWS NOT ALLOWED ON GROUND NEC 250.8 8. SECURE MC WITHIN 12" OF TERMINATIONS - NEC 330 9. NEED SERVICE RECEPTACLE FOR AIR HANDLER - NEC 210.63 10. AIR HANDLER DISCONNECT TO HAVE PROPER WORKING CLEARANCE - NEC 110 DON'T DOUBLE GROUNDING CONDUCTORS -- NEC 110 |
|
| 03/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE CEILING TILES 2. HAVE PANELS OPEN FOR INSPECTION 3. STILL NEED REVISED PLANS 4. PLUG CHECK RECEPTACLES - HAVE REVERSE POLARITY ALSO, HAVE LOOSE RECEPTACLES, CRACKED COVERS 5. FINISH ALARM WIRING 6. INSTA-HOT CKT/WIRING UNDERSIZED 7. HAVE DEAD RECEPTACLES 8. C.B BELOW PANEL TO BE ACCESSIBLE. |