Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/24/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* OK FOR FINAL AIR BALANCE OK |
|
| 04/20/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* DISCONNECT ON ROOF NOT FUSED PER DATA PLATE PLANS REQUIRE AN ANGLE IRON STAND PLANS REQUIRE EF1 & 2 TO BE INTERLOCKED WITH HP-1 TESTED DUCT SMOKE DETECTOR PROVIDE AIR BALANCE REPORT SET THE A/C FAN TO RUN CONTINUALLY DURING OCCUPIED HOURS. |