Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/12/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/24/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING -- 250.8 -- LIGHT FIXTURE 2. EXIT LIGHT NOT WORKING 3. EM LIGHTS AS PER PLAN NOT WORKING 4. SECURE & PROTECT GROUNDING ELECTRODE CONDUCTOR 5. PLEASE VERIFY SERVICE BOND PER 250.58 6. FILL UNUSED OPENING IN AC UNIT 7. TIGHTEN LOOSE FITTINGS 8. OPEN AREAS OF CEILING TO INSPECT VDV CABELING AS PER LAST INSPECTION. |