Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T06CM05997
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/14/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
12/12/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PAINT CONDENSATE PIPE ON ROOF AC OVERFUSED |
|
11/28/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROPERLY IDENTIFY CONDUCTORS USED FOR AC UNIT - MARK UNIT DATA PLATE W/PROPER HEAT STRIP INSTALLED AND FUSE ACCORDINGLY. - YOU CANNOT USE A 5KW HEAT STRIP IN THESE UNITS - SUPPORT CONDUITS PER N.E.C TIGHTEN LOOSE FITTINGS - REMOVE ALL FOIL TAPE FROM OUTDOORS - USE APPROVED SEALANT IF NECESSARY - GRILL MISSING IN CEILING SUPPLY BOX - BATH FOR MISSING RECEPTACLE |
|
11/27/2007 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |