Inspection Status: Partial Approval

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
04/13/2007 PLUMBING - ROUGH, SOIL Partial Approval UNDERGROUND FOR PHOTO LAB
OK TO COVER
WATER TEST OK
03/19/2007 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
1. PLUMBER PLEASE NOTE: ALL FITTINGS, INCLUDING CLEANOUTS, TEST FITTINGS, ETC. ARE TO OPEN IN THE DIRECTION OF FLOW.
NEVER INSTALL A FITTING BACKWARDS!!!
2. OK TO COVER
03/16/2007 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1. NOT INSTALLED PER PLAN
PLAN CALLS FOR PVC - INSTALLED IS ABS
2. HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP.
3. FEMALE THREADS ON ABS NOT PERMITTED IN INACCESSIBLE LOCATION, BESIDES A BLACK TEE IS LISTED AS A VERTICAL SURFACE WALL CLEANOUT
4. WHERE A VENT CONNECTS TO A HORIZONTAL DRAIN, IT SHALL HAVE ITS INVERT TAKEN OFF ABOVE THE DRAINAGE CENTERLINE. EACH VENT SHALL RISE VERTICALLY TO A POINT NOT LESS THAN 6" ABOVE OVERFLOW BEFORE OFFSETTING HORIZ.
5. WET VENTING IS LIMITED TO VERTICAL DRAINAGE PIPING.