Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM05973
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/25/2007 | ELECTRIC - FINAL | Approved | ||
08/01/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* INSPECTION FOR PHOTO LAB ONLY 1. MISSING GUTTER COVERS AT SINK 2. GROUND PANEL PL J-BOX & IDENTIFY ISOLATED GROUND 3. INSPECTION TERMINATED - CONTRACTOR TO CHECK PLANS TO MAKE SURE WORK WAS DONE PER APPROVED PLANS. |
|
06/04/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PLEASE RECALL INSP. CONTR. ON SITE TO MEET WITH INSPECTOR WITH PLANS/PERMIT |
|
04/05/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. NEW PHARMACY OK 2. RECALL WHEN TEMPORARY PHARMACY REMOVED |
|
04/04/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* INSPECTION FOR PHARMACY TRANSFORMER 1. INSTALL K.O BLANKS 2. REMOVE PAINT UNDER LUG 3. XO LUG NOT USED AS LISTED 4. IDENTIFY DISCONNECT 5. PANEL DIRECTORY NOT IN SEE PREVIOUS CORRECTION SHEET - REFEE IF NOT CORRECT NEXT INSPECTION |
|
04/03/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* INSPECTION FOR PHARMACY ONLY 1. NEED PERMANENT PANEL DIRECTORY -- NEC 408.4 2. AT TRANSFORMER: A. NEED BUSHING #4 AND LARGER CONDUCTOR - NEC 300.4F B. IDENTIFY DISCONNECT - NEC 110.2 C. 1" FLEX IS OVERFILLED - NEC 348.22 D. TRANSFORMER AND LOAD SIDE DISCONNECT TO BE BONDED PER NEC 250.30 OK TO OCCUPY PHARMACY |
|
04/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR PHARMACY AREA - PARTIAL INSPECTION 1. HAVE OPEN J-BOX IN CEILING 2. INSTALL PANEL COVER & PANEL DIRECTORY 3. AIM EMERGENCY LIGHTING DOWN & OUT SO THEY WILL BE EFFECTIVE. 4. RECEPTACLES/TRANSFORMER NOT ENERGIZED 5. CB1 MISSING FROM PANEL LP FEEDER SEE PLAN 6. PROVIDE ACCESS TO CEILING TRANSFORMER 7. JOB TO BE WIRED PER PLAN, NEED TO CHECK E-LIGHTS WILL NEED TO PAY REINSPECTION FEE. |