Permit: T06CM05973

Parcel: 105102420


Addresses:

455 E WETMORE RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM05973

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/25/2007 ELECTRIC - FINAL Approved
08/01/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
INSPECTION FOR PHOTO LAB ONLY
1. MISSING GUTTER COVERS AT SINK
2. GROUND PANEL PL J-BOX & IDENTIFY ISOLATED GROUND
3. INSPECTION TERMINATED - CONTRACTOR TO CHECK PLANS TO MAKE SURE WORK WAS DONE PER APPROVED PLANS.
06/04/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PLEASE RECALL INSP. CONTR. ON SITE TO MEET WITH INSPECTOR WITH PLANS/PERMIT
04/05/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. NEW PHARMACY OK
2. RECALL WHEN TEMPORARY PHARMACY REMOVED
04/04/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
INSPECTION FOR PHARMACY TRANSFORMER
1. INSTALL K.O BLANKS
2. REMOVE PAINT UNDER LUG
3. XO LUG NOT USED AS LISTED
4. IDENTIFY DISCONNECT
5. PANEL DIRECTORY NOT IN

SEE PREVIOUS CORRECTION SHEET - REFEE IF NOT CORRECT NEXT INSPECTION
04/03/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
INSPECTION FOR PHARMACY ONLY

1. NEED PERMANENT PANEL DIRECTORY -- NEC 408.4
2. AT TRANSFORMER:
A. NEED BUSHING #4 AND LARGER CONDUCTOR - NEC 300.4F
B. IDENTIFY DISCONNECT - NEC 110.2
C. 1" FLEX IS OVERFILLED - NEC 348.22
D. TRANSFORMER AND LOAD SIDE DISCONNECT TO BE BONDED PER NEC 250.30

OK TO OCCUPY PHARMACY
04/02/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR PHARMACY AREA - PARTIAL INSPECTION
1. HAVE OPEN J-BOX IN CEILING
2. INSTALL PANEL COVER & PANEL DIRECTORY
3. AIM EMERGENCY LIGHTING DOWN & OUT SO THEY WILL BE EFFECTIVE.
4. RECEPTACLES/TRANSFORMER NOT ENERGIZED
5. CB1 MISSING FROM PANEL LP FEEDER SEE PLAN
6. PROVIDE ACCESS TO CEILING TRANSFORMER
7. JOB TO BE WIRED PER PLAN, NEED TO CHECK E-LIGHTS

WILL NEED TO PAY REINSPECTION FEE.