Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/25/2007 | ELECTRIC - ABOVE CEILING | Approved | ||
| 08/01/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 06/04/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/02/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 03/30/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR PHARMACY CEILING ONLY 1. HAVE OVERFILLED J-BOXES -- NEC 314.16 2. ALL BOXES TO BE GROUNDED -- NEC 314.4 3. BLANK ALL UNUSED OPENINGS IN BOXES, RACEWAYS NEC 110 4. FINISH ALL WIRING IN CEILING 5. SECURE MC WITHIN 12" OF TERMINATIONS - NEC 330.30 6. SUPPORT WIRES FOR CABLES/EQUIPMENT TO BE SECURE @ BOTH ENDS - NEC 300.11 7. CEILING SUPPORT WIRES NOT TO SUPPORT OTHER EQUIPMENT 8. PROVIDE DISCONNECTING MEANS FOR SECURITY DOOR MOTOR -- NEC 430.74 |
|
| 03/29/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |