Permit: T06CM05973

Parcel: 105102420


Addresses:

455 E WETMORE RD


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM05973

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
09/25/2007 ELECTRIC - ABOVE CEILING Approved
08/01/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
06/04/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/02/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/30/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR PHARMACY CEILING ONLY
1. HAVE OVERFILLED J-BOXES -- NEC 314.16
2. ALL BOXES TO BE GROUNDED -- NEC 314.4
3. BLANK ALL UNUSED OPENINGS IN BOXES, RACEWAYS
NEC 110
4. FINISH ALL WIRING IN CEILING
5. SECURE MC WITHIN 12" OF TERMINATIONS - NEC 330.30
6. SUPPORT WIRES FOR CABLES/EQUIPMENT TO BE SECURE @ BOTH ENDS - NEC 300.11
7. CEILING SUPPORT WIRES NOT TO SUPPORT OTHER EQUIPMENT
8. PROVIDE DISCONNECTING MEANS FOR SECURITY DOOR MOTOR -- NEC 430.74
03/29/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*