Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/22/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |