Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM05964
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/10/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/09/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* BOTH UNITS 1. PANEL DIRECTORY NOT CORRECT -- NEC 408.4 2. EXTERIOR RECEPTACLE NOT ALLOWED ON BATHROOM RECEPTACLE CKT -- NEC 210.11B3 UNIT 1 1. BEDROOM (WEST) SMOKE DETECTOR NOT INTERCONNECTED |
|
| 08/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION ONLY -- CHECK BOTH UNITS ON ROOFTOP 1. INSTALL PROPER SIZE FUSES 2. CONDENSATE DRAIN NOT TO RUN IN FRONT OF DISCONNECT 3. IDENTIFY WHITE USED AS HOT 4. W.P COVERS NOT ABLE TO CLOSE 5. STRAP FLEX WITHIN 12" OF TERMINATIONS 6. LAUNDRY RECEPTACLE NOT WORKING 7. KITCHEN SWITCH UPSIDE DOWN 8. DISPOSAL RECEPTACLE SET BACK 9. NEED GFI PROTECTION FOR KITCHEN COUNTER RECEPTACLES 10. REFER RECEPTACLE HAS REVERSE POLARITY CHECK PANEL DIRECTORIES - CORRECT, NEAT, LEGIBLE |