Permit: T06CM05956

Parcel: 132166440


Addresses:

4700 S PARK AV #06


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T06CM05956

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/05/2007 FIRE SPKLR - FINAL Approved
04/04/2007 FIRE SPKLR - FINAL Cancelled IVRS - AP canceled
03/21/2007 FIRE SPKLR - FINAL Denied SHALL KEEP ALL STOCK DOWN TO 12' FEET. REMOVE STOCK ON TOP OF RACKS AND DO NOT USE.

IF YOU WANT TO STOCK ABOVE 12', NEED TO HIRE A FIRE PROTECTION ENGINEER OR A LIC. FIRE SPRINKLER CONTRACTOR TO SHOW IF FIRE SPRINKLER SYSTEM CAN BE CHANGED TO HANDLE STORAGE OVER 12'.

REPLACE ALL DAMAGE FOIL ON CEILING.
03/20/2007 FIRE SPKLR - FINAL Cancelled IVRS - AP canceled
02/15/2007 FIRE SPKLR - FINAL Partial Approval NEED AP FOR 2ND PHASE
01/26/2007 FIRE SPKLR - FINAL Approved
01/22/2007 FIRE SPKLR - FINAL Not ready for Inspection
01/03/2007 FIRE SPKLR - FINAL Not ready for Inspection 1 head too far off wall.
Fix all insulation.
Twisted pipe
Install all ceiling tiles