Permit: T06CM05951

Parcel: 132160470


Addresses:

1500 E BENSON HY

Inspection Status: Approved

Inspection History: FIREWALL/FIREBARRIER/FIRESTOP

Date Description Inspector Results Comments
02/21/2007 FIREWALL/FIREBARRIER/FIRESTOP Approved IVRS - Inspection :*
02/14/2007 FIREWALL/FIREBARRIER/FIRESTOP Not ready for Inspection IVRS - Inspection :*
FIRE BARRIER SEPARATES TENANTS PER DETAIL AND CODE ANALYSIS SHEET G 0.0
02/12/2007 FIREWALL/FIREBARRIER/FIRESTOP Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/06/2007 FIREWALL/FIREBARRIER/FIRESTOP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 12" ADDRESS DISPLAY PER PIMA COUNTY ZONING REQUIRED
2) FINISH SITE WORK
3) FINISH IN BATHROOMS MUST MEET CHAPTER 12 REQUIREMENTS SHEETROCK IS NOT ACCEPTABLE BEHIND WATER CLOSETS
4) INSTALL GRAB BARS PER ANSI 117.1
5) PROPERLY FIRE STOP 1 HR WALL
6) PROPERLY FINISH BOTH SIDES OF 1 HR WALL
7) WOOD INFILL IS NOT 1 HR WALL
01/31/2007 FIREWALL/FIREBARRIER/FIRESTOP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1 HR PARTITION MUST BE 5/8 GYPSUM WALL BOARD OR FIRE RATED ON BOTH SIDES. NEED COMPLIANCE WITH
SECTION 708 IBC REGARING FIRE PARTITION.