Permit: T06CM05949

Parcel: 12801005H

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T06CM05949

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
06/11/2007 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
06/07/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
UNDER SLAB GREASE WASTE & SANITARY WASTE OK
1. SHALL SEE PIPE WRAPS & FLOOR SINK INSTALL PRIOR TO CONCRETE POUR BACK.
06/06/2007 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
1. PROVIDE CORRECT VENT FOR FLOOR SINK AT WATER HEATER.
2. FLOW CONTROL FOR GREASE TRAP TO BE IN VISIBLE AND ACCESSIBLE LOCATION ABOVE GRADE WITH FULL SIZE PIPING FROM FLOW CONTROL TO GREASE TRAP.
3. NO THREADED WASTE FITTING IN UNACCESSIBLE LOCATION.
06/04/2007 PLUMBING - ROUGH, SOIL Cancelled