Permit: T06CM05949

Parcel: 12801005H

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM05949

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/11/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
ALL SIGNS FIELD EVALUATED BY U.L
07/11/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. RECEIVED LETTER OF MC USE
2. COMPLETE ITEM 1 FROM INSPECTION ON 7/2/07
SIGNS NEED TO MEET REQUIREMENTS OF NEC 600

OK TO FILE FOR TEMP C OF O
07/06/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. COMPLETE ITEMS 1, 2, 4

OK TO FILE FOR TEMP C OF O
07/03/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. COMPLETE ITEMS 1, 2, 3, 4, 5, 9 FROM INSPECTION
ON 7/2/07
2. SIGNS NEED TO MEET REQUIREMENTS OF NEC ARTICLE 600
07/02/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SIGNS HAVE NO LISTING OR LABELING MARK
2. PROVIDE LETTER FROM ENGINEER FOR USE OF MC CABLE
3. CANNOT USE CORD FOR PERMANENT WIRING
4. NEED REVISED SET OF DRAWINGS SHOWING ALL ELECTRIC WORK THAT WAS DONE
5. IDENTIFY WHITE WIRES USED AS PHASE CONDUCTORS
6. INSTALL PANEL DIRECTORY
7. TERMINATE GROUND PROPERLY AT PANEL BOARD
8. SEAL OPEN KNOCKOUTS IN DISCONNECT FOR WALK IN
9. FUSES NOT PROPERLY SIZED FOR WALK IN
10. GROUNDING CONDUCTORS #6 AND SMALLER TO BE CONTINUOUSLY IDENTIFIED -- 250.119
11. WIRING NOT SIZED PROPERLY PER NEC 314.28