Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/11/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* ALL SIGNS FIELD EVALUATED BY U.L |
|
| 07/11/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. RECEIVED LETTER OF MC USE 2. COMPLETE ITEM 1 FROM INSPECTION ON 7/2/07 SIGNS NEED TO MEET REQUIREMENTS OF NEC 600 OK TO FILE FOR TEMP C OF O |
|
| 07/06/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. COMPLETE ITEMS 1, 2, 4 OK TO FILE FOR TEMP C OF O |
|
| 07/03/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. COMPLETE ITEMS 1, 2, 3, 4, 5, 9 FROM INSPECTION ON 7/2/07 2. SIGNS NEED TO MEET REQUIREMENTS OF NEC ARTICLE 600 |
|
| 07/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SIGNS HAVE NO LISTING OR LABELING MARK 2. PROVIDE LETTER FROM ENGINEER FOR USE OF MC CABLE 3. CANNOT USE CORD FOR PERMANENT WIRING 4. NEED REVISED SET OF DRAWINGS SHOWING ALL ELECTRIC WORK THAT WAS DONE 5. IDENTIFY WHITE WIRES USED AS PHASE CONDUCTORS 6. INSTALL PANEL DIRECTORY 7. TERMINATE GROUND PROPERLY AT PANEL BOARD 8. SEAL OPEN KNOCKOUTS IN DISCONNECT FOR WALK IN 9. FUSES NOT PROPERLY SIZED FOR WALK IN 10. GROUNDING CONDUCTORS #6 AND SMALLER TO BE CONTINUOUSLY IDENTIFIED -- 250.119 11. WIRING NOT SIZED PROPERLY PER NEC 314.28 |