Inspection History Details
Inspection Status: Approved
Inspection History: STUCCO MESH
Permit Number - T06CM05930
Inspection Description - STUCCO MESH
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/15/2007 | STUCCO MESH | Approved | IVRS - Inspection :* | |
| 02/05/2007 | STUCCO MESH | Not ready for Inspection | IVRS - Inspection :* | |
| 01/31/2007 | STUCCO MESH | Not ready for Inspection | IVRS - Inspection :* 1) FIX HOLE CUT IN SHEARWALL, FOR 3" ABS AT GARAGE 2) PEX TOO CLOSE TO CAN KIT 3) DUCT MOVED FOR CAN LIGHT KIT 4) CHECK LEAK IN PEX CONNECTION PANTRY CEILING 5) FLUSH OUT HEADERS 1ST FLOOR 6) COMPLETE ALL H.D.'S 7) ATTIC VENTS MISSING 8) BOTTOM PLATES NOT NAILED 2ND FLOOR NORTH BED CLOSET 9) BANG PLATE 2ND FLOOR ROMEX #10 WIRE FRONT BEDROOM, WEST BATH PEX 1) #1 SHEAR 2ND FLOOR SINKERS AT 12" ON CENTER, #9 SHEAR AT 4" ON CENTER 11) EXTEND SLOPED WALL AT STAIR FOR GUARD RAIL 12) 1ST FLOOR A.B.'S MARKED ON FLOOR |