Permit: T06CM05930

Parcel: 141314750

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T06CM05930

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
01/25/2007 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
01/10/2007 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) NEED DETAIL FOR PORCH, FRAMING NOT ON PLAN
01/05/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 6' 2 X 4 AT 6' ON CENTER MISSING PER 2/SD4
2) LSL MISSING PER 17/SD4
3) HORIZONTAL STRAP MISSING PER 9/SD2
4) 3" ON CENTER STAGGERED NAIL PATTERN REQUIRED OVER SHEARWALLS PER 18/SD4
5) CS20 STRAP REQUIRED FROM ENTRY GLU LAM TO TRIMMERS PER 9/SD2
6) GLU LAM AT STAIRWAY NOT PER PLAN-NEED STRAPS AND POSTS PER 9/SD2
7) PORCH BEAMS NOT TIED DOWN
8) TWO TRIMMERS REQUIRED AT 2 X 12 HDR IN DEN
9) STOPPED INSPECTION-BUILD PER PLAN