Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T06CM05925
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/06/2007 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* - CORRECTIONS HAVE BEEN MADE - OK TO SHEETROCK - EXTEND UPPER COMBUSTION AIR DUCT UP INTO ATTIC ABOVE INSULATION - WILL CHECK ON FINAL - CONDENSATE DRAINS CANNOT TERMINATE ONTO THE ROOF - PROVIDE SCREEN IN T-TOPS ON ROOF |
|
| 08/23/2007 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* - COMBUSTION AIR DUCTS NOT INSTALLED PER PLAN - EXHAUST DUCT CANNOT BE REDUCED FROM 4" TO 3" - INSULATE SHEETMETAL DUCTS IN ATTIC WITH A VAPOR BARRIER INSULATION MIN. R4.2 |