Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM05925
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/06/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/11/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* KITCHEN AND ACTIVITY ROOM EMERGENCY LIGHTING TO BE POWERED BY NORMAL LIGHTING CKT FOR AREA - NEC 700.12F |
|
| 01/14/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EMERGENCY LIGHTING TO BE FED BY NORMAL LIGHTING CKT FOR AREA - NEC 700.12F 2. PROVIDE GFI PROTECTION FOR KITCHEN COUNTER RECEPTACLES 3. IDENTIFY PANEL DIRECTORY - NEC 408.4 4. INSTALL RANGE ANTI-TIP DEVICE 5. ALARM RECEPTACLE SHOWS OPEN GROUND - SO DO SEVERAL OTHERS. RECEPTACLES WITH NO GROUND MUST HAVE GFI PROTECTION OR BE OF THE 2 WIRE NON-GROUNDING TYPE RECEPTACLE WORK TO BE DONE BY QUALIFIED ELECTRICIAN |