Permit: T06CM05925

Parcel: 10603035A


Addresses:

131 E MOHAVE RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM05925

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/06/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/11/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
KITCHEN AND ACTIVITY ROOM EMERGENCY LIGHTING TO BE POWERED BY NORMAL LIGHTING CKT FOR AREA - NEC 700.12F
01/14/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EMERGENCY LIGHTING TO BE FED BY NORMAL LIGHTING CKT FOR AREA - NEC 700.12F
2. PROVIDE GFI PROTECTION FOR KITCHEN COUNTER RECEPTACLES
3. IDENTIFY PANEL DIRECTORY - NEC 408.4
4. INSTALL RANGE ANTI-TIP DEVICE
5. ALARM RECEPTACLE SHOWS OPEN GROUND - SO DO SEVERAL OTHERS.
RECEPTACLES WITH NO GROUND MUST HAVE GFI PROTECTION OR BE OF THE 2 WIRE NON-GROUNDING TYPE RECEPTACLE

WORK TO BE DONE BY QUALIFIED ELECTRICIAN