Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T06CM05921
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/02/2007 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
03/01/2007 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) OSB ROOF SHEATHING NOT STAPLED TO BLOCKS PER DETAIL 2-1.5 2) ROOF SHEATHING MUST SPAN 3 MEMBERS 3) REFEE WILL APPLY |
|
02/26/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PER DETAIL 2/1.5 ALTERNATE TRANSFER ? 2) MISSING SP-4 CLIPS THROUGHOUT 3) PROVIDE SAFE ACCESS TO ROOF |
|
02/23/2007 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection :* 1) HOLDOWNS NOT COMPLETE 2) ROOF SHEATHING MUST BE NAILED TO BIRD BLOCKS |
|
02/15/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* HOLDDOWNS MISSING FRONT BEDROOM |
|
02/14/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLY WITH PREVIOUS NOTE #2 2) NAIL OFF SHEARWALL PANELS UNDER ROOF PER 7 SD3, CHECK ALL SHEAR TANSFER NAILING |
|
02/07/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HOLDOWNS MISSING AT FRONT BEDROOM 2) NO ROOF ACCESS |