Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM05916
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/28/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* 800A SERVICE DISCONNECT OK |
|
| 02/27/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* INSTALL REJECT PINS FOR FINAL OK TO CLEAR NEW SERVICE FOR SUITE #200 OK PER 250-142B EXC#2 TO BOND CT CAY FROM 2002 NEC |
|
| 02/20/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK TO INSTALL CEILING TILES - BLANK OFF OPEN BOX 2. PARALLED CONDUCTORS TO HAVE SAME CHARACTERISTIC NEC 310.4 FOR SERVICE |
|
| 02/16/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* WORK NOT READY |
|
| 02/09/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 02/07/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEUTRAL NOT ALLOWED TO GROUND ENCLOSURES ON LOAD SIDE OF SERVICE-NEC 250.142 B 2) INSTALL FUSES NEC 310 3) GROUND RACEWAYS/EQUIPMENT WITH EQUIPMENT GROUND NEC 250.122 4) K.O. BLANKS IN SIDES TO BE RAIN TITE-NEC 110 5) MOUNT EQUIPMENT SECURELY TO WALL-NEC 110.13 NOT PLASTIC ANCHORS IN MASONRY 6) PARALLEL CONDUCTORS TO BE SAME TYPE, LENGTH ETC. NEC 310.4 7) PARALLEL AND CKT CONDUCTORS TO BE RAN THROUGH NIPPLES PER NEC 303.3 B & B1 |
|
| 01/30/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER ALL 2ND LEVEL FLOOR BOXES |
|
| 01/12/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK FLOOR BOXES IN UNIT #130 |
|
| 01/09/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK INTERIOR ELECTRICAL COVER IN WALLS FOR 2ND LEVEL |
|
| 01/05/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : There is no access to the site.| 920* LOCKED NO ACCESS NO SUITE # POSTED |
|
| 01/04/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO POUR FLOOR BOXES (2 @ NORTH END) |
|
| 01/02/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL IN WALLS FLOOR RECEPTACLES DENIED -- NEC 348.12 |
|
| 12/29/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) INSTALL UNIT NUMBER ON SPACE 2) FINISH INTERMEDIATE |