Permit: T06CM05916

Parcel: 11205019B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM05916

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/28/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
800A SERVICE DISCONNECT OK
02/27/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
INSTALL REJECT PINS FOR FINAL
OK TO CLEAR NEW SERVICE FOR SUITE #200
OK PER 250-142B EXC#2 TO BOND CT CAY
FROM 2002 NEC
02/20/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK TO INSTALL CEILING TILES - BLANK OFF OPEN BOX
2. PARALLED CONDUCTORS TO HAVE SAME CHARACTERISTIC NEC 310.4 FOR SERVICE
02/16/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
WORK NOT READY
02/09/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
02/07/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEUTRAL NOT ALLOWED TO GROUND ENCLOSURES ON LOAD SIDE OF SERVICE-NEC 250.142 B
2) INSTALL FUSES NEC 310
3) GROUND RACEWAYS/EQUIPMENT WITH EQUIPMENT GROUND NEC 250.122
4) K.O. BLANKS IN SIDES TO BE RAIN TITE-NEC 110
5) MOUNT EQUIPMENT SECURELY TO WALL-NEC 110.13 NOT PLASTIC ANCHORS IN MASONRY
6) PARALLEL CONDUCTORS TO BE SAME TYPE, LENGTH ETC. NEC 310.4
7) PARALLEL AND CKT CONDUCTORS TO BE RAN THROUGH NIPPLES PER NEC 303.3 B & B1
01/30/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ALL 2ND LEVEL FLOOR BOXES
01/12/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK FLOOR BOXES IN UNIT #130
01/09/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK INTERIOR ELECTRICAL COVER IN WALLS FOR 2ND LEVEL
01/05/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
There is no access to the site.| 920*
LOCKED NO ACCESS
NO SUITE # POSTED
01/04/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO POUR FLOOR BOXES (2 @ NORTH END)
01/02/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL IN WALLS
FLOOR RECEPTACLES DENIED -- NEC 348.12
12/29/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) INSTALL UNIT NUMBER ON SPACE
2) FINISH INTERMEDIATE