Permit: T06CM05893

Parcel: 116157330

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06CM05893

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/30/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
01/29/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. DW DRAIN HOSE SHALL BE SECURED AS HIGH AS POSSIBLE AND IN NO CASE LESS THAN 2" BELOW FLOOD LEVEL
2. VENT BELOW FLOOD LEVEL SHALL HAVE DRAINAGE FITTINGS
3. SINK LEAKING
INSPECTION STOPPED

RECALL FOR INSPECTION AFTER WATER TESTING ALL FIXTURES AND CORRECTING CODE VIOLATIONS
01/17/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
01/15/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
NO ACCESS - GATE LOCKED
01/04/2008 PLUMBING - FINAL Cancelled IVRS - RI canceled
01/04/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
ALL OTHER UNITS IN THIS COMPLEX HAD SEWER/HCS 03055 AND YARDWATER 03040. IF THESE INSPECTION CODES ARE NOT ON YOUR PERMIT CARD, IT IS YOUR RESPONSIBILITY TO HAVE THE NECESSARY CODES ADDED TO YOUR PERMIT AND IF COVERED, UNCOVER THE WORK AND CALL IN THE INSPECTIONS. THIS WAS DISCUSSED TWO MONTHS AGO WITH LES. CONTINED "NOT READY" WILL RESULT IN A REINSPECTION FEE.