Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM05893
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/21/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
06/21/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. TIGHTEN CONDUCTOR UNDER GROUND SCREWS FOR METAL BOXES. 2. DEMO OLD WIRING AND DEVICES IN WALLS/CEILING 3. KITCHEN 2 GANG OVERFILLED 4. KITCHEN COUNTER RECEPTACLES TO BE NOT MORE THAN 24" FROM END OF COUNTER OR RECEPTACLE IN THAT AREA SEE NEC 210.52 5. INSTALL ADDITIONAL NAIL PLATES AS NEEDED 6. PROVIDE BACK SUPPORT FOR BOXES ALONG FURRED OUT KITCHEN WALL 7. FINISH PLUMBING ROUGH IN 8. BEDROOM RECEPTACLES NOT LAYED OUT PROPERLY SEE 210.52 9. BATH GFI CKT TO BE DEDICATED - NOT WITH EXTERIOR RECEPTACLE 10. HAVE HANGING WIRE AT BEDROOM SLIDER |
|
06/20/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |