Permit: T06CM05883

Parcel: 133050340


Addresses:

8711 E LANCASTER RD

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
03/30/2007 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
03/27/2007 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REBAR MUST BE AT LEAST 3" ABOVE SOIL
2) GAS LINE CANNOT RUN UNDER BLDG. MUST BE REROUTED PRIOR TO POUR
3) YOU MAY NEED TO ADD GAS TO YOUR PERMIT AND MOVE THE METER OR CONTACT S.W. GAS TO REROUTE SUPPLY LINE