Permit: T06CM05876

Parcel: 110103020


Addresses:

3180 N SWAN RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/05/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/03/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. PROPERLY INSTALL SURFACE RACEWAYS FOR VDV CABLING
2. PANEL SCHEDULE TO BE AS PER 408.4 - NO GENERAL LABELING - NO ABBREVIATIONS
3. SUPPORT VDV CABLING ABOVE CEILING
4. VERIFY GROUND PATH OF SPRINKLER PIPE FOR SERVER ROOM GROUND
5. INSTALL ALL COVER PLATES
6. ROOF FITTINGS LOOSE AT ALL AC UNITS
7. REDUCING WASHERS INSTALLED IMPROPERLY
8. PLEASE PROVIDE LETTER FOR EXTRA FIXTURES AT TRACKS