Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - PROGRESS
Permit Number - T06CM05866
Inspection Description - PLUMBING - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/12/2007 | PLUMBING - PROGRESS | Approved | IVRS - Inspection :* | |
01/09/2007 | PLUMBING - PROGRESS | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE AIR ADMITTANCE VALVE FOR FLOOR SINK VENT WITH CORRECT TRANSITION COUPLING. 2. PERMANENT CAP UNUSED 2" RISER FOR DRAINAGE UNDER SINK. 3. PROVIDE 2% MINIMUM FALL FOR SINK DRAINAGE PER PLAN. 4. EXPANSION TANK SHALL BE SECURED & SUPPORTED. |
|
01/04/2007 | PLUMBING - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* |