Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/28/2007 | FRAMING | Approved | IVRS - Inspection :* | |
| 03/26/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) AT STAIR #9 SHEARWALL CMST14 STRAP REQUIRED 1ST/2ND FLOOR 2) 3/4" A.B.'S AT 24" REQUIRED SAME WALL 1ST FLOOR 3) EAST WALL 1ST FLOOR 1/2" A.B.'S AT 24" 4) MISSING GFCI RECEPTACLE MASTER LAV |