Permit: T06CM05850

Parcel: 140292410


Addresses:

6268 S EARP WASH LN

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/30/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/25/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BOXES USED ARE NOT APPROVED FOR FANS
2) PROTECT WIRES GOING INTO BOX WITH BUSHING OR ROMEX CONNECTOR
3) EXPOSE WIRES AT SWITCHES
4) EXPOSE PVC FOR INSPECTION
5) SCHEDULE 80 PVC REQUIRED WHERE EXPOSED