Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/29/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/24/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SUPPORT REFER LINES TO CONDENSORS CLAMP TO BLOCKS PERMANENTLY ID ALL EQUIPMENT TIGHTEN LOOSE ELEC. CONNECTIONS SUPPORT CONDUITS CONDENSORS OVERFUSED 2 EA PROVIDE A SERVICE RECEPTACLE ON ROOF WITHIN 25' OF ALL EQUIPMENT. |
|
| 08/23/2007 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* PROVIDE ROOF ACCESS |