Permit: T06CM05829

Parcel: 116157330

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T06CM05829

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/20/2007 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
OK FOR SHEETROCK
03/06/2007 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SCREWS IN BATHROOM EXHAUST TOO LONG & BLOCKING BACKDRAFT DAMPER.
2. FINISH WORK IN WATER HEATER ROOM
3. RELOCATE CONDENSATE DRAIN
4. WATER HEATER VENT MUST BE MIN. 5' IN HEIGHT.