Permit: T06CM05828

Parcel: 116157330

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
06/28/2007 FRAMING Approved IVRS - Inspection :*
05/01/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE FIREBLOCKING IN CONCEALED SPACES ON LOCATION WITH ELECTRICAL WIRES THROUGH WALL AND ATTIC IN ACCORDANCE WITH THE SECTIONS 717.1, 717.2 IBC
FIREBLOCKING SHALL CONSIST OF 2 INCH NOMINAL LUMBER OR ONE THICKNESS OF 3/4" WOOD STRUCTURAL PANEL WITH JOINT BACKED BY BLOCKS, ONE THICKNESS OF 3/4" PARTICLE BOARD, 5/8" GYPSUM BOARD TYPE X, 1/2" GYPSUM HARD TYPE C OR WITH ANY APPROVED MALENAL IN ACCORDANCE WITH THE SECTION 717.2.1
04/06/2007 FRAMING Partial Approval IVRS - Inspection :*
1) LAUNDRY ROOM ONLY