Permit: T06CM05816

Parcel: 14108534A

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM05816

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/23/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
01/31/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
FLOOR DRAINS; TRAP PRIMERS, FLOOR CLEANOUTS
LIME PITE & INSPECTION PIT INSTALL IN ROOM 106 OK
01/30/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
AIR TEST 3" FROM SUMP PIT ROOM #104 UP OVERHEAD TO 3' EXTERIOR OF BUILDING OK PER PLAN
SHALL RETEST CONTINUATION OF PIPING
PIPING IS PRIMED & WRAPPED FOR CONCRETE
01/29/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. PROVIDE TEST ON WELDED PIPE
2. PROVIDE WRAP ON PIPING UNDER SLAB
01/25/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WATER TEST OK IN GEL MIXING ROOM #104
01/24/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. ROOM #102 - TEST IN WALL OK FOR WATER & WASTE & VENT
2. PROD. LAB #103 - TEST IN WALL OK FOR WATER & WASTE & VENT.
3. GEL MIXING #108 WASTE & VENT PIPING TEST OK
4. PROVIDE NEW TEST FOR WATER AFTER MOVING WATER PIPING IN WALL.
01/04/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. TEST ON UNDERGROUND PIPING PVC 2" OK IN ROOM
#102 & #103
2. PARTIAL OK FOR STEM WALL IN ROOM 105-106 TEST ON UNDERGROUND WASTE PIPING OK
01/02/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
12/28/2006 PLUMBING - INTERMEDIATE Cancelled IVRS - RI canceled