Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/21/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* INSPECTION FOR 2ND LEVEL DROP CEILING 1. CORD AND PLUG CONNECTED EQUIPMENT NOT ALLOWED ABOVE SUSPENDED CEILING -- NEC 400.8 (5) 2. ALARM PANEL TO BE ACCESSIBLE AND NEED CONNECTORS FOR CONNECTORS (CCTV) WIRING NOT COMPLETE, PROVIDE LADDER, CALL WHEN FINISHED. |