Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM05815
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/22/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/21/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* INSPECTION FOR 2ND LEVEL DROP CEILING 1. CORD AND PLUG CONNECTED EQUIPMENT NOT ALLOWED ABOVE SUSPENDED CEILING -- NEC 400.8 (5) 2. ALARM PANEL TO BE ACCESSIBLE AND NEED CONNECTORS FOR CONNECTORS (CCTV) WIRING NOT COMPLETE, PROVIDE LADDER, CALL WHEN FINISHED. |