Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 03/21/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 03/19/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 03/16/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 02/15/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK BATHROOM CEILINGS |
|
| 02/13/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* NEED TO GO THROUGH WIRING FOR CEILINGS ABOVE BATHROOMS -- 1. STRAP EMT 2. STRAP FLEX 3. PULL AND MAKE UP CKT'S 4. GROUND ALL J-BOXES 5. HAVE OVERFILLED BOXES 6. HAVE MISUSED/OVERFILLED WIRENUTS 7. ALL BOXES TO BE ACCESSIBLE OK TO COVER CEILING IN S.W CLOSET HARD LID |