Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/21/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 03/19/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR SERVICE/PANELS/TRANSFORMER AREA 1. ALL AUXILARY GUTTERS TO BE INSTALLED PER NEC 366 2. EXISTING TRANSFORMER APPEARS TOO CLOSE TO BACK WALL - PROVIDE INFORMATION FROM MANUFACTURE ALLOWING CURRENT INSTALLATION CLEARANCE. 3. TRANSFORMER BONDING TO BE PER NEC 250.30 4. RACEWAYS BETWEEN PANELS TO BE BONDED PER NEC 250.30 5. CONDUCTORS IN RACEWAYS TO MEET THE REQUIREMENTS OF NEC 310.15 B2 6. INSURE SERVICE MEETS BONDING REQUIREMENTS OF NEC 250.104 PARTIAL INSPECTION ONLY |
|
| 02/07/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALL COVER FOR ELECTRICAL |
|
| 01/26/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL TO FLOOR RECEPTACLES (3) NO DIVIDER IN BOXES |