Permit: T06CM05815

Parcel: 10408001C

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM05815

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/22/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/21/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/19/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR SERVICE/PANELS/TRANSFORMER AREA
1. ALL AUXILARY GUTTERS TO BE INSTALLED PER NEC 366
2. EXISTING TRANSFORMER APPEARS TOO CLOSE TO BACK WALL - PROVIDE INFORMATION FROM MANUFACTURE ALLOWING CURRENT INSTALLATION CLEARANCE.
3. TRANSFORMER BONDING TO BE PER NEC 250.30
4. RACEWAYS BETWEEN PANELS TO BE BONDED PER
NEC 250.30
5. CONDUCTORS IN RACEWAYS TO MEET THE REQUIREMENTS OF NEC 310.15 B2
6. INSURE SERVICE MEETS BONDING REQUIREMENTS OF
NEC 250.104

PARTIAL INSPECTION ONLY
02/07/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALL COVER FOR ELECTRICAL
01/26/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL TO FLOOR RECEPTACLES (3)
NO DIVIDER IN BOXES