Permit: T06CM05807

Parcel: 137055220

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM05807

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/13/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
12/12/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SEISMIC WIRES USED FOR SUPPORT TO BE TIED OFF BOTH ENDS.
2. SUPPORT MC WITHIN 12" AT TERMINATIONS AND AT 6' INTERVALS PER NEC
3. GROUND J-BOXES