Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/21/2007 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* PROVIDE 20X30 ACCESS TO EXISTING FAN COIL PROVIDE APPROVED BASE UNDER CONDENSOR ON ROOF SECURE ELEC. CONDUITS ON ROOF PERMANENTLY ID UNITS OK TO USE KITCHEN |
|
| 08/14/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - DRAIN PAN MUST BE 1 1/2" LARGER THAN FAN COIL ON ALL SIDES - RELOCATE DRAIN LINE BLOCKING ACCESS TO FAN COIL - PROVIDE MIN. 20 X 30 ACCESS OPENING TO REMOVE FAN COIL #8 |
|
| 08/02/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - RELOCATE CONDENSATE DRAIN BLOCKING ACCESS TO FAN COIL. - RELOCATE DISCONNECT MOUNTED ON DATA PLATE - PROVIDE A SECONDARY DRAIN PAN UNDER FAN COIL AS PER PLANS. |
|
| 07/10/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* FINISH INSTALLING DIFFUSERS IN LOBBY OK CEILING TILES |
|
| 06/15/2007 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |