Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM05803
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/11/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 08/27/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/21/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | - DATA SIGNAL CABLING OVER GREATROOM NEEDS TO BE SUPPORTED OFF GRID - FIRE ALARM DEVICES NOT INSTALLED YET |
|
| 08/02/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* - SEE NOTES FROM INSP. 7/10/07 - 110V KITCHEN OUTLETS TO BE GFI PROTECTED AS PER 210 NEC |
|
| 07/11/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. ENSURE SMOKE DETECTOR GETS INSTALLED IN CEILING AT LOBBY 2. OK DROP CEILING ABOVE RECEPTION DESK |
|
| 07/10/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - MC CABLE TO BE INDIVIDUALLY SUPPORTED TO STRUCTURE WITHIN 12" OF TERMINATIONS & AT 6' INTERVALS PER NEC DO NOT SUPPORT TO OTHER UTILITIES TRADES, HANGERS OR SUPPORTS. INSTALL SEISMICS FOR CAN LIGHTS |
|
| 06/14/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |