Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/28/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/18/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MAINTAI WORKING CLEARANCE IN FRONT OF PV SERVICE 110.26 2. SEPARATE NEUTRALS AND GROUNDS AT SUB-PANEL 250.24 3. #8 GROUNDING ELECTRODE TO HAVE A PATH BACK TO SERVICE NOT A NEUTRAL. 4. CHASE NIPPLES NOT AN APPROVED FITTING. 5. SEALING DEVICES NEEDED FOR ENTRANCES ABOVE CURRENT CARRING PARTS 6. SUPPLEMENTARY ELECTRODE CONDUCTOR TO BE INSTALLED PER 250 AND INSTRUCTION MANUAL. 7. LABEL NEEDED AT MAIN SERVICE PANEL. |