Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM05801
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/06/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/05/2007 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
04/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. AC UNIT BREAKERS AT PANELS TO BE DERATED TO 30 AMPS -- 12 CONDUCTORS IN CONDUIT -- 50% 2. NOT ALL HOLES SEALED ON AC DISCONNECTS 3. OPEN WIRING ON J-BOXES ON ROOF & OPEN WIRING ON EAST SIDE OF BUILDING WITH WIRE NUTS ONLY -- REMOVE WIRE OR BOX OFF 4. ALL PANELS TO BE PROPERLY MARKED 5. PNL A - GROUNDS & NEUTRALS CANNOT BE ON SAME TERMINAL - MUST BE ISOLATED 6. NEED TO PROPERLY CLOSE OFF OPENING IN PNL A TOP SIDE NEW ENTRY 7. PANEL SCHEDULE ON NEW PANEL DOES NOT REFLECT PLAN 8. HALL SURFACE MOUNTED FIXTURES SHOWN ON PLAN TO BE WRAP AROUND NOT EXPOSED - BULB IS TOO LOW 9. PLEASE MAKE A PROPER SCHEDULE FOR PNL A 10. POWER POLE TO BE INSTALLED FOR FINAL 11. ALL DATA & COMMUNICATION WIRING TO BE LIFTED OFF GRID & SUPPORTED -- NOT LAYING ON GRID. |
|
03/30/2007 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
03/28/2007 | ELECTRIC - FINAL | Not ready for Inspection | 1. ROOF-SEAL ALL HOLES ON DISCONNECTS, PROPERLY AND PERMANENTLY TO ALL DISCONNECTS WITH AC# & CIR. 2. SEAL ALL ELECTRICAL PENETRATIONS THRU ROOF. 3. MAIN CONDUIT BRINGING AC FEEDERS TO ROOF HAS TOO MANY CIRCUTI CARRING CONDUCTORS - DERATION NEEDED. 4. HALL AT EAST EXIT NOT READY 5. NOT ALL RECEPTS ENERGIZED, KIT ALSO 6. PANEL SCHEDULE NOT IN 7. WATER HEATER REQUIRES DISCONNECT 8. STILL HANGING FIXTURES 9. LIGHTS IN COMM ROOM MISSING 10. INSTALL EM LTS. 11. AC UNIT IN COMM ROOM MISSING PLEASE INSPECT FOR JOB TO BE READY PRIOR TO CALL FOR FINAL. |