Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T06CM05796
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/11/2007 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
06/05/2007 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : There is no access to the site.| 920* |
|
05/04/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) SERVICE OK |
|
05/03/2007 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* BOND SERVICE RISER PER NEC 250.92 |
|
04/19/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. OK GROUND RODS & GROUND RING AT CELL TOWER 2. OK PVC CONDUITS INSIDE STEM WALLS AT EQUIPMENT LOCATION. 3. SITE LOCKED BEHIND MCGRAW'S STEAKHOUSE |
|
04/09/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK GROUND RING AND GROUND RODS AT EQUIPMENT LOCATION 2) LOCATED BEHIND MC ? STEAK HOUSE |