Permit: T06CM05789

Parcel: 110160460


Addresses:

5991 E GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/17/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
1. CLEAN SURFACE UNDER LUG IN DISCONNECT - 250.12

OK FINAL AFTER CORRECTIONS
03/14/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
03/12/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250.8
2. ID EQUIPMENT GROUNDING CONDUCTORS ROOF AC'S
250.119
3. FINISH ITEMS #1 & 3 PREVIOUS INSPECTION
01/17/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOND DISCONNECT ENCLOSURE
2. CONNECTOR AT WATER HEATER - INSTALL
3. BOXES MORE THAN 1/4" FROM BOX TO SURFACE - 314.20
4. PANEL DIRECTORY TO BE AS PER 408.4 - NO ABBREVIATIONS
NO GENERAL LABELING
5. LIGHTS - SWITCHING NOT AS PER PLANS
6. OUTSIDE FIXTURES NOT AS PER PLANS

ROOF:
7. TIGHTEN LOOSE FITTINGS
8. LABEL DISCONNECTS
9. SUPPORT MAINTENANCE RECEPTACLE BOX AND COVER TO BE AS PER 406.8
08/31/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*