Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM05789
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/17/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1. CLEAN SURFACE UNDER LUG IN DISCONNECT - 250.12 OK FINAL AFTER CORRECTIONS |
|
03/14/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
03/12/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250.8 2. ID EQUIPMENT GROUNDING CONDUCTORS ROOF AC'S 250.119 3. FINISH ITEMS #1 & 3 PREVIOUS INSPECTION |
|
01/17/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOND DISCONNECT ENCLOSURE 2. CONNECTOR AT WATER HEATER - INSTALL 3. BOXES MORE THAN 1/4" FROM BOX TO SURFACE - 314.20 4. PANEL DIRECTORY TO BE AS PER 408.4 - NO ABBREVIATIONS NO GENERAL LABELING 5. LIGHTS - SWITCHING NOT AS PER PLANS 6. OUTSIDE FIXTURES NOT AS PER PLANS ROOF: 7. TIGHTEN LOOSE FITTINGS 8. LABEL DISCONNECTS 9. SUPPORT MAINTENANCE RECEPTACLE BOX AND COVER TO BE AS PER 406.8 |
|
08/31/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |