Permit: T06CM05789

Parcel: 110160460


Addresses:

5991 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM05789

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/17/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/09/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. MAINTAIN CLEARANCE 110.26
2. POST BOND FOR TEMP POWER FOR TEST AND ADD 02062 TO PERMIT

*408.4, 700.12
11/07/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. MAINTAIN WORKING CLEARANCES PER 110.26
2. VERIFY 1ST GROUNDING ELECTRODE
3. BOND RISERS & NIPPLES AS PER 250.92
4. INSTALL ALL MANUFACTURES BARRIERS
5. PREVENT OBJECTIONABLE CURRENT 250.6 PARALLEL PATHS
6. VERIFY WATER BONDING
7. INSTALL FUSES & REJECTION PINS
8. INSTALL MAIN BONDING JUMPER AT DISCONNECT
9. SUPPORT ELECTRIC AS PER 300.11
10. MANUFACTURES CLIPS TO BE EFFECTIVE IF SCREWS 4 ON CORNERS
11. SUPPORT CONDUITS AS PER CODE 3' FROM BOXES
12. BOX OVERFILLED
09/27/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS
2) SUPPORT M/C CABLE 12" OF EXHAUST FANS
09/21/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROTECT MC CABLE INSIDE OF CHANNELS
2. PROPERLY INSTALL EXHAUST FANS

OK OUTSIDE LIGHT & SOFFIT CANS
OK WALLS EXCEPT ROOM #4
NO LIDS
08/31/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CONSTRUCTION POWER TO OUTSIDE OF BUILDING ONLY
2. MAINTAIN WORKING CLEARANCES 110.26
3. SUPPORT M/C CABLE WITH APPROVED STRAPS ON VERTICAL SURFACES
4. PREVENT DIELECTRIC CONTACT
5. PROTECT PVC CONDUIT AT BASE PLATE
6. SUPPORT EMT CONDUIT AS PER CODE
7. BOXES OVERFILLED 314.16
8. FILL UNUSED OPENINGS IN BOXES
9. MC CABLE NOT APPROVED AS PER PLANS
10. PVC NOT ALLOWED ABOVE GRADE AS PER PLANS
11. BUSHING NEEDED ON CONDUIT 352.46, 300.4
12. IDENTIFY GROUNDING EQUIPMENT CONDUCTOR