Permit: T06CM05781

Parcel: 12101103E

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/07/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
03/05/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE A SUITE NUMBER ON ROOFTOP EQUIPMENT
CONTRACTOR PLEASE LEAVE A CONTACT NUMBER
01/10/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
PERMANENTLY I.D CONDENSORS WITH UNIT # AND SUITE #
PERMANENTLY I.D DISCONNECTS
SECURE CONDENSORS TO PLATFORM.
DISCONNECT OVERFUSED.
PROVIDE INSTALL INSTRUCTIONS FOR CONDENSATE PUMP.
OK TO APPLY FOR TEMP C OF O
PHASE A ROOMS 108-110