Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T06CM05781
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/26/2007 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* DAVID 609-8066 OK FOR CEILING TILE PROVIDE A HOSE CLAMP WHERE PLASTIC HOSE CONNECTS TO COPPER TUBE. TERMINATE DRAINS ON ROOF DIRECT TO AN EXISTING DRAIN ON ROOF. CANNOT TERMINATE INTO A SEWER VENT. CONDENSORS ARE OVERFUSED. |
|
01/10/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* |