Permit: T06CM05781

Parcel: 12101103E

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/04/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/27/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NO EQUIPMENT
03/05/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
NEED TO SEE MEDICAL EQUIPMENT
01/19/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK TCO PHASE 1
1. UNWIRE UNUSED POLE AS PER MCGETRICK INSTRUCTIONS IN CONTROL CABINET.
01/11/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINISH ITEMS #2, 4, 5
01/10/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. VDV CABELING TO BE SUPPORTED AS PER 725.6 & 300.11
2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20
3. WHERE IS DISCONNECTING MEANS FOR ROOM A/C UNIT.
4. CONTROL CABINET IS 3 PHASE WIRED. POWER SUPPLIED IS ONLY SINGLE PHASE.
5. NEED TO SEE MEDICAL EQUIPMENT TO VERIFY LISTINGS.