Permit: T06CM05780

Parcel: 141185710

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/05/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
AIR BALANCE OK
CORRECTIONS HAVE BEEN MADE
OK FOR FINAL
10/30/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
EF-1 NOT BALANCED CORRECTLY
REMOVE FOIL TAPE FROM VENT CONNECTORS
EVERYTHING ELSE OK
09/27/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- FURNACE VENTS MUST INCREASE TO 4" AT THE OUTLET ON FURNACE.
- PROVIDE MIN. 1" CLEARANCE FROM INSULATION
- LOW VOLTAGE WIRE AT PACKAGE UNIT MUST BE IN CONDUIT
- PERMANENTLY ID DISCONNECTS & UNITS
- PROVIDE AIR BALANCE REPORT
- SEE BLDG. INSPECTOR FOR TEMP C OF O