Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/28/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* FAILURE TO HAVE ACCESS ON DAY OF CALL OUT WILL RESULT IN REFEE -- 12:00 |
|
| 06/01/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* THIS INSPECTION FOR 03040 YARD WATER 2" FROM BUILDING STUB PER REDLINE ON SITE PAGE X-1.0 TO AREA OF ISLAND AT SOUTHEAST CORNER OK |
|
| 05/21/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WASTE & VENT TO ABOVE CEILING WATER TEST OK 1. COMPLETE VENT THRU ROOF WATER PIPING THRU BUILDING 2" STUBBED OUT OK 2. PROVIDE INSULATION ON HOT & HOT RETURN PIPING PER PLAN AND 2004 ENERGY CONSERVATION CODE. 3. TRAP PRIMER REQUIRES (2) TRAP PRIMERS OR (1) WITH DISTRIBUTION DEVICE. 4. CLOSET FLANGES TO BE INSPECTED PRIOR TO SETTING STOOLS, SHALL BE ON FINISH FLOOR & SECURED. |