Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2007 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* WATER TEST FOR PIPING IN & OUT OF EJECTOR SUMP OK WITH VENT FOR SUMP OK |
|
| 08/23/2007 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* WATER TEST 3" VENT FROM SUMP OK 1. SHALL PROVIDE CAST IRON VENT ABOVE GRADE AT BUILDING 2. SHALL INSTALL DISCHARGE PIPING PER 2003 UPC 3. SHALL WATER TEST SEWER EJECTOR PUMP |
|
| 08/20/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) WATER TEST NOW 4" BLDG SEWER FROM EXISTING TO 5' FROM LIFT STATION SUMP 2) 4" GRAVITY SEWER FROM 10' FROM SUMP TO HCS CONNECTION TO PUBLIC SEWER OK 3) SHALL SEE CONTINUATION OF PIPING WITH TEST INTO AND OUT OF SUMP |
|
| 05/31/2007 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/29/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* SHADING MATERIAL AROUND 4" ABS OK FROM BUILDING THRU 2-WAY & BACKWATER VALVE TO 92' EAST OK |
|
| 05/25/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 4" ABS BUILDING SEWER FROM 4" BUILDING DRAIN STUB GOES EAST 92' INCLUDING CLEANOUTS WITH BACKWATER VALVE INSTALLED AND INLINE CLEANOUT STUB UP WATER TEST OK ONLY. 1. BEFORE COVERING PROVIDE 1/2-MATERIAL AS SHADING AND BEDDING WITH INSPECTION AND PROOF OF NEED FOR BACKWATER VALVE WHEN UPSTREAM MANHOLE IS INSTALLED. |
|
| 04/13/2007 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* WATER TEST OK 1. ALL PIPING SHALL NOT BE DIRECTLY EMBEDDED IN CONCRETE. PROVIDE PIPE WRAPS. 2. SHALL PROVIDE DETAIL & HAVE BUILDING INSPECTOR APPROVED PIPES THRU BUILDING FOOTING. |
|
| 04/09/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) WATER TEST UNDERGROUND THRU BLDG TO 2-WAY CLEANOUT OK 2) SHALL SEE PIPE WRAPS AND CORRECTION FOR PIPE THRU FOOTING PRIOR TO CONCRETE |
|
| 04/06/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) WATER TEST THRU BLDG TO 3' EXTERIOR N.E. CORNER PARTIAL APPROVAL 2) SHALL PROVIDE CORRECT DRAINAGE FITTING FOR PLAN TO 2003 UPC FOR BACK TO BACK FLOOR DRAINS AT MENS AND WOMENS RESTROOMS 3) NO PIPING SHALL PASS DIRECTLY THRU BLDG FOOTINGS AT AREAS OF END OF LINE CLEANOUTS. MAKE CORRECTIONS AND RETEST THOSE AREAS 2) |